KFD2-SL2-EX1.B安全柵
型號:
KFD2-SL2-EX1.B
| Signal type | Digital Output |
|---|---|
| Functional safety related parameters | |
| Safety Integrity Level (SIL) | SIL 2 |
| Supply | |
| Connection | Power Rail or terminals 14+, 15- |
| Rated voltage | 20 ... 30 V DC |
| Power consumption | max. 1.7 W at 45 mA output current |
| Input | |
| Connection side | control side |
| Connection | terminals 7, 8 |
| Input current | approx. 3 mA at 24 V DC |
| Signal level | 1-signal: 16 ... 30 V DC 0-signal: 0 ... 5 V DC |
| Output | |
| Connection side | field side |
| Internal resistor | 272 Ω |
| Current | ≤ 45 mA |
| Voltage | ≥ 11.7 V |
| Open loop voltage | min. 24 V |
| Connection | terminals 1+, 2- or 3- |
| Output rated operating current | 45 mA |
| Output signal | These values are valid for the rated operating voltages from 20 ... 30 V DC. |
| Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
| Galvanic isolation | |
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Power supply/Output | reinforced insu |