NBN40-U2-E0 現(xiàn)貨直發(fā) 傳感器
型號:
NBN40-U2-E0
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | NPN | |
| Rated operating distance | 40 mm | |
| Installation | non-flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 32.4 mm | |
| Actual operating distance | 36 ... 44 mm typ. 40 mm | |
| Reduction factor rAl | 0.31 | |
| Reduction factor rCu | 0.3 | |
| Reduction factor r304 | 0.74 | |
| Reduction factor rBrass | 0.39 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 150 Hz | |
| Hysteresis | typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | ≤ 2 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 μA at 25 °C | |
| No-load supply current | ≤ 20 mA | |
| Operating voltage indicator | LED, green | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1510 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated ≤36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | screw terminals | |
| Core cross-section | max. 2.5 mm2 | |
| Housing material | PA/metal with epoxy powder coating | |
| Sensing face | PA | |
| Degree of protection | IP68 / IP69K | |
| Mass | 225 g | |
| Note | Tightening torque: 1.8 Nm (housing) Tightening torque: 1.0 Nm (Screw terminal) | |